10-44 Scheduler Interface
event. If connected, the State Machine functional block will respond to the
updated input.
Note: When Debug Enable is On and DebugNext is updated and On, the Event
Scheduler emits the next event. While the EventScheduler is looking up the next
event, it also is responding to the network variable polls at a slowed rate. If you
select the Stop Automatic Display option of the LonMaker Browser Message
dialog box, you can stop message flow. DebugNext will update, the
EventScheduler will stop at the next event, and network variable polls will be
responded to normally.