CPD 3000 Lighting Controller
Integration Guide
Version 1
078-0485-01A
Przeglądanie stron 0
1 2 3 4 5 6 ... 22 23

Podsumowanie treści

Strona 1 - @echelon

@echelon® CPD 3000 Lighting Controller Integration Guide Version 1 078-0485-01A

Strona 2

10 Application as Function Block The application for the CPD 3000 is developed as a sole function block. The UFPTli

Strona 3 - Welcome

CPD 3000 Integration Guide 11 Table 1 LC Network UNVTfaults Variables Implemented on the CPD 3000 Network Variable Type Notes nviLampV

Strona 4 - Table of Contents

12 transactions to capture level control feedback, environmental variables, and alarm conditions. This network vari

Strona 5 - Guidelines

CPD 3000 Integration Guide 13 supplyVoltage SNVT_volts Measured supply voltage 0.1V resolution. This value is updated every second. supplyCur

Strona 6 - Installation

14 Broadcast Support The CPD 3000 supports the limited broadcast message support implemented on SmartServer 2.1 Firm

Strona 7 - European Model

CPD 3000 Integration Guide 15 nciPowerProfile UNVTpowerProfile Defines the nominal power measured at 5 commanded nviLampValues 0.5%, 25%, 50%,

Strona 8

16 CoolDownTmwill extend this time.as required when controlling certain lamp types such as HPS.rampTm SNVT_time_se

Strona 9 - Interface

CPD 3000 Integration Guide 17 lower limit of the PWM output with the nviLampValue is at 0.5%. Limit to 0-255. (Default value – 0). Use this

Strona 10

18 Working with the CPD 3000 and the target driver/ballast is required to determine the limits for the best scaling

Strona 11

CPD 3000 Integration Guide 19 controlled to defaultLev (Default –0s; which means HB checking is disabled) nciPowerProfile UNVTpowerProfile D

Strona 12

Echelon, LONWORKS, LONMARK, and the Echelon logo are trademarks of Echelon Corporation registered in the United States and other countries. Other

Strona 13

20 alarm is triggered. (Defaults value - 65.0 C) nciLimits.lampFailFault SNVT_lev_cont The threshold of power drop

Strona 14 - Broadcast Support

CPD 3000 Integration Guide 21 LowSupplyVoltage Measured voltage is nciLimits.voltageLow % below the voltage defined by nciControlCfg.supplyVol

Strona 15 - UNVTControlCfg

22 The CPD 3000 uses the nciPowerProfile table to define the expected power at five equally spaced nviLampValue.valu

Strona 16

CPD 3000 Integration Guide 23 E WARMUP state timer expires OR commanded OFF Updates to nviLampValue are delayed until out of WARMUP. F COOLDO

Strona 17 - Analog Control

CPD 3000 Integration Guide iii Welcome Echelon’s Power Line based lighting controller, the CPD 3000, can be used to control outdoor street lig

Strona 18 - LC Alarm Management

iv Table of Contents Welcome ... iiiCPD 3000 I

Strona 19

CPD 3000 Integration Guide 5 1 CPD 3000 Installation and Wiring Guidelines The CPD 3000 Lighting Controller can be installed within the light

Strona 20

6 Installation Installation for the CPD 3000 OLC uses the following steps. It is important to disconnect line volt

Strona 21

CPD 3000 Integration Guide 7 Wiring Specification and Diagram Here are the wiring specifications and diagram for US and European models of th

Strona 22 - CPD 3000 Control Sequence

8 Two AWG 16 wires for filtered power output (both models) Red Line Out Blue Neutral Out or Line 2 Out The 0-10V

Strona 23

CPD 3000 Integration Guide 9 2 CPD 3000 Lighting Controller Interface The CPD 3000 Lighting Controller borrows much of its interface from the