i.LON SmartServer 2.0 Programmer’s Reference
15-11
15.4.1
Using the List Function on Modbus Data Points
You can use the List function to retrieve a list of Modbus data points on the SmartServer. The List
function takes an <iLonItem> element that has an xSelect statement with a MOD_Dp_Cfg type as its
input, as shown in the example below.
Request (use an xSelect statement to return all the Modbus data points on the SmartServer)
<List xmlns="http://wsdl.echelon.com/web_services_ns/ilon100/v4.0/message/">
<iLonItem>
<xSelect>//Item[@xsi:type="MOD_Dp_Cfg"]</xSelect>
</iLonItem>
</List>
Alternatively, you can filter the Modbus data points returned by the List function to those on a specific
device by including the <UCPTname>of the parent device in the xSelect statement, or you can filter
the Modbus data points returned using the <UCPTname> and <UCPTlastUpdate> data point
properties.
Request (use an xSelect statement to return all the Modbus data points on a specific device)
<List xmlns="http://wsdl.echelon.com/web_services_ns/ilon100/v4.0/message/">
<iLonItem>
<xSelect>//Item[@xsi:type="MOD_Dp_Cfg"][starts-with(UCPTname,"Net/Modbus Channel/LAE_LCD15_2")]
</xSelect>
</iLonItem>
</List>
Request (use an xSelect statement to return all the Modbus data points that were updated after a
specific time)
<List xmlns="http://wsdl.echelon.com/web_services_ns/ilon100/v4.0/message/">
<iLonItem>
<xSelect>//Item[@xsi:type="MOD_Dp_Cfg"][UCPTlastUpdate&gt;"2008-03-31T00:00:00"]
</xSelect>
</iLonItem>
</List>
Request (return all the Modbus data points of a specific type based on name)
<List xmlns="http://wsdl.echelon.com/web_services_ns/ilon100/v4.0/message/">
<iLonItem>
<xSelect>//Item[@xsi:type="MOD_Dp_Cfg"][contains(UCPTname,"Alrm")]</xSelect>
</iLonItem>
</List>
Response
<List xmlns="http://wsdl.echelon.com/web_services_ns/ilon100/v4.0/message/">
<Item>
<UCPTname>Net/Modbus Channel/LAE_LCD15_1/VirtFb/Alrm_1</UCPTname>
<UCPTannotation>Dp_In_Out;xsi:type="MOD_Dp_Cfg"</UCPTannotation>
<UCPThidden>0</UCPThidden>
</Item>
<Item>
<UCPTname>Net/Modbus Channel/LAE_LCD15_1/VirtFb/Alrm-Prb1_1</UCPTname>
<UCPTannotation>Dp_In_Out;xsi:type="MOD_Dp_Cfg"</UCPTannotation>
<UCPThidden>0</UCPThidden>
</Item>
<Item>
<UCPTname>Net/Modbus Channel/LAE_LCD15_1/VirtFb/Alrm-Prb2_1</UCPTname>
<UCPTannotation>Dp_In_Out;xsi:type="MOD_Dp_Cfg"</UCPTannotation>
<UCPThidden>0</UCPThidden>
</Item>
<Item>
<UCPTname>Net/Modbus Channel/LAE_LCD15_1/VirtFb/Alrm-Prb3_1</UCPTname>
<UCPTannotation>Dp_In_Out;xsi:type="MOD_Dp_Cfg"</UCPTannotation>
<UCPThidden>0</UCPThidden>
</Item>
</List>